EN
GCS low voltage withdrawable switch cabinet
Product Introduction:
Tel:400-000-6707
Add:No. 258, Weiqi Road, Economic Development Zone, Yueqing City, Zhejiang Province
<< >>
Product details

Introduction
The GCS device is suitable for power distribution systems in industries such as power plants, petroleum, chemical engineering, metallurgy, textiles, and high-rise buildings. In large power plants and petrochemical systems where a high degree of automation is required and interfacing with computers is necessary, the GCS device serves as a low-voltage complete power distribution device for distribution, centralized motor control, and reactive power compensation in power generation and supply systems. These systems have a three-phase AC frequency of 50 (60) Hz, a rated working voltage of 380V (or 400V, 660V), and a rated current of up to 4000A.

Model meaning​



Use conditions​

>Surrounding air temperature not above +40℃, not below -5℃; 24h average temperature not above +35℃; when exceeding, capacity reduced running is required according to actual situations;
>Indoor use, altitude not above 2000m at the use place;
>Surrounding air relative humidity is not above 50% at +40℃; high relative humidity is allowed at low temperature, for example, 90% at +20℃; influences of condensation may be generated in view of temperature changes;
>Gradient not above 50° with the vertical face during device installation; whole set of cabinet array is relatively level (in line with GBJ232-82 standard);
>The device should be installed at places without violent vibration or impact, or places where the electric appliance components will not be influenced by due corrosion.


Technical parameters​

NameParameter
Main circuit rated voltage (V)AC 380(400)、(660)
Auxiliary circuit rated voltage (V)AC 220、380(400)、DC 110、220
Rated frequency (Hz)50(60)
Rated insulation voltage (V)660(1000)
Rated current (A)Horizontal bus≤ 4000
Vertical bus (MCC)1000
Bus rated short-time withstand current (kA,1 s)50,80
Bus rated peak withstand current (kA/0.1s)105 ,176
Power frequency test voltage (V/1min)Main circuit2500
Auxiliary circuit1760
BusThree-phase five-line systemA.B.C.PE.N
Protection levelIP30、IP40


Outline dimension drawing​


Universal cabinet codeABCDRemark
GCS-TG1010-410001000850956Communication cabinet
GCS-TG0810-48001000650956Electrifying cabinet
GCS-TG0808-4800800650756Electrifying cabinet
GCS-TG0608-4600800450756Electrifying cabinet


Order information​

Please provide following technical information during ordering:
>All models of the product (including main circuit scheme No. and auxiliary circuit scheme No.);
>Combination sequence drawing of main circuit system;
>Electric schematic diagram of auxiliary circuits;
>List of devices in the cabinet
>Setting parameters such as voltage, current and time in circuits;
>Other special requirements not conforming to regular use of the product.
​


Tel
400-000-6707
Mobile Web
COPYRIGHT © 2021 CHINA·LANZI ELECTRIC CO., LTD. ALL RIGHTS RESERVED
Z. ICP. B. 2024071628-1 Technical support: Dingnuo Media

Z.G.W.A.B. 33038202004776

News Information
Application Area
Contact Us
COPYRIGHT © 2021 CHINA·LANZI ELECTRIC CO., LTD. ALL RIGHTS RESERVED
Z. ICP. B. 2024071628-1
Technical support: Dingnuo Media

Z.G.W.A.B. 33038202004776

Go Top